A compact heat exchanger network has been developed in Flownex to serve as a reference for further heat exchanger modelling.
PROJECT FILE
The network can be downloaded by clicking on the download button below:
NETWORK DESCRIPTION
The network, shown in Figure 1, consists of two separate flow paths: a gas-side path and a liquid-side path. Heat is transferred between the streams through a separating wall, modelled using a Composite Heat Transfer component.
The gas-side flow path uses CO₂ at an inlet pressure of 10 000 kPa and temperature of 400°C, with a mass flow rate of 20 kg/s. The liquid-side flow path operates at an inlet pressure of 500 kPa and temperature of 300°C, with a mass flow rate of 15 kg/s.
The network represents a liquid-to-gas channel ratio of 1:4, with four gas channels for every liquid channel. The gas channels are arranged in a serpentine configuration. Although the actual flow arrangement may involve cross-flow regions, the heat exchanger is approximated as a purely counter-flow arrangement in this example.
The geometrical and heat transfer inputs for the pipe and Composite Heat Transfer components are calculated in a linked Excel worksheet titled Input Sheet 1, shown in Figure 2.
The worksheet uses colour coding to distinguish between inputs and calculated values. Orange cells contain user-defined geometrical parameters (channel radius, length and plate thickness), unhighlighted cells contain intermediate calculations, and blue cells contain the final values linked to the Flownex component inputs. Intermediate calculations use Excel formulas, which can be viewed by selecting the corresponding cell, allowing the inputs to be traced and updated when modifying the geometry.
Figure 3 shows the gas-side wall temperature distribution along the heat exchanger. The incremented temperature results illustrate how the wall temperature varies along the gas-side flow path as heat is transferred between the two streams.
The current model provides a simplified representation of the heat exchanger using an equivalent counter-flow arrangement. Further refinement could involve discretising the heat exchanger into smaller sections to capture local cross-flow effects and variations in temperature and heat transfer along the flow paths.
RUNNING THE SIMULATION
- Solve Steady State.
Once the solution has converged, review the gas-side temperature distribution plot.