This Flownex model simulates a Battery Energy Storage System (BESS) comprising liquid-cooled battery stacks and air-cooled chillers operating on an R134a refrigeration cycle. The model allows users to investigate the effects of battery heat generation, cooling pump speed, ambient air temperature and air mass flow rate on system performance.
Both steady-state and transient simulations can be performed to examine the resulting changes in temperatures, mass flow rates and refrigeration cycle operating conditions.
PROJECT FILE
The network can be downloaded by clicking on the download button below:
NETWORK DESCRIPTION
This network represents a Battery Energy Storage System (BESS) and consists of two network pages: BESS and BESS Compound. The BESS network represents two BESS stacks connected to a single air-cooled chiller, while the BESS Compound network represents four BESS stacks served by two air-cooled chillers connected in parallel.
The BESS network, shown in Figure 1, consists of two stacks, each containing four battery units modelled as compound components. The heat generation rate of each stack can be adjusted during the simulation using the corresponding slider above the stack.
The cooling liquid is cooled by the chiller before being distributed to the two BESS stacks in parallel. It absorbs heat from the batteries before the two branches recombine and return to the pump. The pump speed can be adjusted during steady-state and transient simulations to investigate the effects of changes in mass flow rate on battery temperatures.
The BESS Compound network, shown in Figure 2, represents an expanded system comprising four BESS stacks and two air-cooled chillers connected in parallel. The individual stacks and chiller systems are encapsulated in compound components to simplify the network layout. The complete system can be simulated under transient conditions to investigate the effects of changes in battery heat generation, pump speed and chiller operating conditions. The resulting changes in battery temperatures, mass flow rates and chiller performance can be monitored throughout the simulation.
Each battery unit, shown in Figure 3, contains a liquid cooling loop with a composite heat transfer element that transfers the heat generated within the battery to the circulating cooling liquid. Four battery units are then grouped into a stack compound component, which is used to represent each BESS stack in the BESS Compound network.
The chiller network, shown in Figure 4, represents a vapour-compression refrigeration cycle using R134a as the refrigerant. The cycle consists of a compressor, condenser, expansion nozzle and evaporator. The coefficient of performance (COP) is calculated and displayed, while the refrigerant operating points are plotted on a temperature–entropy (T–s) diagram. During transient simulations, the operating points update to reflect changes in operating conditions.
At the condenser, heat extracted from the battery cooling loop is rejected to the surrounding air. The air inlet temperature and mass flow rate can be adjusted during the simulation to investigate their effects on chiller performance and battery temperatures.
RUNNING THE SIMULATION
Load "SS" snap.
Solve steady state.
Run the transient simulation. Adjust the operating parameters using the sliders to investigate their effects on the system performance.